The Scully WX System is certified by exida® as SIL2
FEATURES
The ordering information below is for FM and FMC approved units. For International ATEX and SIL approved models see:
Control Units
| Part Number | Description | DIM X | DIM Y | Depth |
|---|---|---|---|---|
| 07851 ST-15-WX3 | Three-Channel Sensing Point Control Unit | 16″ | 24″ | 7.25″ |
| 07852 ST-15-WX4 | Four-Channel Sensing Point Control Unit | 16″ | 24″ | 7.25″ |
| 07853 ST-15-WX5 | Five-Channel Sensing Point Control Unit | 24″ | 30″ | 7.25″ |
| 07854 ST-15-WX6 | Six-Channel Sensing Point Control Unit | 24″ | 30″ | 7.25″ |
| 07855 ST-15-WX7 | Seven-Channel Sensing Point Control Unit | 24″ | 30″ | 7.25″ |
| 07856 ST-15-WX8 | Eight-Channel Sensing Point Control Unit | 24″ | 30″ | 7.25″ |
| 07857 ST-15-WX9 | Nine-Channel Sensing Point Control Unit | 30″ | 36″ | 7.25″ |
| 07858 ST-15-WX10 | Ten-Channel Sensing Point Control Unit | 30″ | 36″ | 7.25″ |
| 07859 ST-15-WX11 | Eleven-Channel Sensing Point Control Unit | 30″ | 36″ | 7.25″ |
| 07860 ST-15-WX12 | Twelve-Channel Sensing Point Control Unit | 30″ | 36″ | 7.25″ |
| Product Range: | Gasoline through #6 oil, waste oil, chemicals, water, etc. Consult Scully for specific application questions. |
| Controls: | Alarm test push button; alarm silence circuit with push button and automatic reset |
| Indicator Lights: | Green = Power On; Red = Alarm Condition |
| Response Time: |
High-level: .05 seconds maximum Low-level: 3-7 seconds |
| Enclosure: | NEMA 4 style for indoor/outdoor use |
| Power Requirements: | 115 VAC, +/- 15%, 50–60HZ, 20 watts maximum. Also available in 240 VAC models; consult Scully for details |
| Electrical Connections: | Internal Terminal Strips |
| Output Provisions: | External Alarm, 115VAC, 3 A max. Individual channel SPDT contacts, rated 5A- 250 VAC |
| Compatible Sensors: | Refer to technical data sheets; 60635, 60715 |
| Intrinsic Safety Information: | The ST-15-WX control units can be mounted in any non-hazardous area and utilize oil tight controls and indicators. Internal circuitry provides intrinsically safe (I.S.) output, for probe connections. This output is rated for Class I, Div 1, Group D hazardous areas. |
| SIL Certification: | IEC 61508 Certified SIL2 HFT=0 SIL3 HFT=1 |
| Chemical Applications: | Refer to technical data sheet 67100 |
Datasheets: